6
|
Technical data
Service manual
405
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
Symbol Component
Major function
Y12S
Solenoid Valve (oil
separator 2 oil
return)
Controls amount of oil return from oil
separator to compressor.
S1NPH Pressure sensor
(high)
Detects discharge pressure. In cooling: mainly
to control fan speed of outdoor unit. In
heating: mainly to control compressor
capacity.
S1NPL
Pressure sensor
(low)
Detects suction pressure. In cooling: mainly to
control compressor capacity. In heating:
mainly for the calculation of suction superheat.
S1PH
Pressure switch
(high, M1C
discharge)
Prevents excess high pressure during
malfunction. Stops operation when triggered.
S2PH
Pressure switch
(high, M2C
discharge)
Prevents excess high pressure during
malfunction. Stops operation when triggered.
R1T
Thermistor (air)
Detects ambient temperature. Used for
correction of discharge temperature and
judging defrost condition.
R21T
Thermistor (M1C
discharge)
Detects discharge temperature of the
compressor
R22T
Thermistor (M2C
discharge)
Detects discharge temperature of the
compressor
R3T
Thermistor (liquid,
main)
Used to detect pipe temperature of receiver
inlet.
R4T
Thermistor (upper
heat exchanger,
liquid pipe)
This detects temperature of liquid pipe
between the air heat exchanger and upper
heat exchanger electronic expansion valve.
Used to make judgements on recovering or
discharging refrigerant to the refrigerant
regulator.
R5T
Thermistor (lower
heat exchanger,
liquid pipe)
This detects temperature of liquid pipe
between the air heat exchanger and lower
heat exchanger electronic expansion valve.
Used to make judgements on recovering or
discharging refrigerant to the refrigerant
regulator.
R6T
Thermistor
(sub‑cool heat
exchanger, gas
pipe)
Detects sub‑cool heat exchanger outlet
temperature on injection line. Used to keep
the sub‑cool heat exchanger outlet superheat
constant.
R7T
Thermistor
(sub‑cool heat
exchanger, liquid
pipe)
Detects liquid pipe temperature of outdoor
unit to indoor units. Mainly used to calculate
sub-cool.