6
|
Technical data
Service manual
457
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
3
Push BS2 18 times.
Result:
Mode 2 setting 18 is addressed:
4
Push BS3 1 time; the value which is returned (depending on the actual field
situation), is the status of the setting. In the case of [2‑18], default value is "0",
which means the function is not active.
Result:
Mode 2 setting 18 is addressed and selected, return value (e.g. 0) is
the current setting situation.
5
To change the value of the setting, push BS2 till the required value appears on
the 7‑segment display indication. When achieved, define the setting value by
pushing BS3 1 time. To start operation according to the chosen setting,
confirm again by pushing BS3.
6
To leave the monitoring function, push BS1 1 time.