458
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
6.9.4 Mode 1: Field settings
In mode 1 you can make field settings to configure the system. The LEDs give a binary representation of the
setting/value number.
(
*
)
This column shows the number of times you have to push the SET button (BS2) to access the field setting.
N°
(
*
)
Item
Display
Content
0
Main/sub outdoor unit
1.00
-
Undefined
0
Main unit
1
Sub 1 unit
2
Sub 2 unit
1
Low noise operation status
1.01
0
Not in low noise operation
1
In low noise operation
2
Demand operation status
1.02
0
Not in demand operation
1
In demand operation
3
Automatic back up operation status
1.03
0
Off
1
On
4
Defrost selection set
1.04
0
Slow
1
Normal
2
Quick
5
Te set
1.05
0
Automatic
1
3 ˚C
2
6 ˚C
3
7 ˚C
4
8 ˚C
5
9 ˚C
6
10 ˚C
7
11 ˚C
6
Tc set
1.06
0
Automatic
1
41 ˚C
2
42 ˚C
3
43 ˚C
4
44 ˚C
5
45 ˚C
6
46 ˚C
7
48 ˚C
7
Cool/heat unified address
1.07
Possible 0 ˜ 31
8
Low noise / demand address
1.08
Possible 0 ˜ 31
9
Airnet address
1.09
Possible 0 ˜ 63