6.9.5 Mode 2: Field settings
In mode 2 you can make field settings to configure the system. The LEDs give a binary representation of the
setting/value number.
(
*
)
This column shows the number of times you have to push the SET button (BS2) to access the field setting.
(
**
)
The bold content is the default setting.
N°
(
*
)
Item
Display
Content
(
**
)
0
Cool/heat selection
2.00
0
Individual
1
Master (DTA104A6* option required)
2
Slave (DTA104A6* option required)
1
Cool/heat unified address
2.01
0
Possible 0-31
2
Low noise/demand address
2.02
0
Possible 0-31
5
Indoor unit forced fan H
2.05
0
Disabled
1
Enabled
6
Indoor unit forced thermo ON
2.06
0
Disabled
1
Enabled
8
Te setting
2.08
0
Auto
1
3 ˚C
2
6 ˚C
3
7 ˚C
4
8 ˚C
5
9 ˚C
6
10 ˚C
7
11 ˚C
9
Tc setting
2.09
0
Auto
1
41 ˚C
2
42 ˚C
3
43 ˚C
4
44 ˚C
5
45 ˚C
6
46 ˚C
7
48 ˚C
10
Defrost selection setting
2.10
0
Short
1
Normal
2
Long
12
Low noise/demand operation by
external input
2.12
0
Disabled
1
Enabled
13
AirNet address
2.13
0
Possible 0-63 (0 is not a valid airnet
address)