VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
6.9.6 Overview of field settings for indoor units
The overview lists all possible settings for the indoor units. The availability of the setting depends on the indoor
unit type, see "Field settings as per type indoor unit".
Bold content is default setting
.
Mode
1
st
code
Description function
2
nd
code
Description selection
10(20)
0
Filter contamination heavy / light
01
Filter contamination: light LL
2500 hr / flat 200 hr
02
Filter contamination: heavy LL
1250 hr / flat 100 hr
1
Long life filter type
01
Long life filter
02
Super long life filter
04
Oil guard filter
2
Air thermistor selection
01
Combined control
02
Only the return air thermistor
03
Only the remote controller
thermistor
3
Display filter sign
01
Display
02
No display
4
Spare
--
--
5
Remote controller thermistor
visible by central control device in
group wiring P1P2
01
No
02
Yes
6
Air thermistor selection in group
wiring P1P2
01
Return air thermistor (individual
units)
02
Thermistor designated by field
set 20-2 (see above)
7
Absence delay detecting time
(presence sensor)
01
30 minutes
02
60 minutes
8
Compensation air sensor heating
01
Add 2.0°C to measurement air
sensor
02
Measurement air sensor
9
Spare
--
--