2
|
Troubleshooting
Service manual
47
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
INFORMATION
When the power is switched ON, the outdoor unit main PCB checks all expansion
valve coil windings by current check.
1
Perform a check of the main PCB. See
290].
Possible cause:
Faulty main PCB.
2
Perform a check of the upper heat exchanger expansion valve. See
244].
Possible cause:
Faulty upper heat exchanger expansion valve.
3
Perform
a
check
of
all
refrigerant
side
thermistors.
See
348].
Possible cause:
Faulty refrigerant side thermistor(s).
4
Perform a check of the refrigerant low pressure sensor. See
Possible cause:
Faulty refrigerant low pressure sensor.
5
Check if the refrigerant circuit is correctly charged. See
Possible cause:
Refrigerant overcharge.
6
Check if the power supply is conform with the regulations. See
Possible cause:
▪
Faulty or disturbance of the power supply (imbalance >10%),
▪
Power drop,
▪
Short circuit.
7
Perform a power reset. If the error disappears and is raised again after a
while, check for the presence of an external source causing electrical noise.
See
Possible cause:
External source may cause interference.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.27 E9-23-24-25 – Electronic expansion valve (Y2E) failure
Main error code
Sub error code
Unit
E9
23
Main
24
Sub 1
25
Sub 2
Summary of Contents for VRV IV+