2
|
Troubleshooting
Service manual
71
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
Possible cause:
Faulty de–icer thermistor or connector fault.
4
Check if the refrigerant circuit is correctly charged. See
Possible cause:
Refrigerant overcharge.
5
Check for the presence of non‑condensables and/or humidity in the
refrigerant circuit. See
363].
Possible cause:
Non‑condensables and/or humidity in the refrigerant circuit.
6
Perform a check of the evaporator side expansion valve. See
Possible cause:
Faulty evaporator side expansion valve.
7
Check for objects near the indoor unit that may block the airflow. See
372].
Possible cause:
Airflow of the indoor unit is blocked.
8
Clean the air filters of the indoor unit(s). See service manual of the respective
indoor unit(s).
Possible cause:
Faulty or clogged air filter.
9
Adjust external static pressure setting for ducted type indoor units, if
necessary.
10
Perform a check of the indoor unit fan motor. See service manual of the
respective indoor unit(s).
Possible cause:
Faulty indoor unit fan motor.
11
Perform
a
check
of
the
discharge
pipe
thermistor.
See
348].
Possible cause:
Faulty discharge pipe thermistor or connector fault.
12
Perform a check of the refrigerant high pressure sensor. See
Possible cause:
Faulty refrigerant high pressure sensor.
13
Perform a check of the indoor unit air thermistors. See service manual of the
respective indoor unit(s) for more information.
Possible cause:
Faulty indoor unit air thermistor(s).
14
Check all indoor units operation in heating mode. Check for room
temperatures below 20°C. Check if caution disappears once rooms heat‑up. If
NOT, continue checking the cause of the wet operation.
Possible cause:
Indoor room temperature too low when in heating mode. Too
cold rooms might create more subcool resulting in wet operation.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.