Troubleshooting
Service manual
75
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
2.3.50 H3-03-05-07 – Transmission error on inverter PCB A6P
Main error code
Sub error code
Unit
H3
03
Main
05
Sub 1
07
Sub 2
INFORMATION
Main, Sub 1 and Sub 2 indications are relevant in multiple outdoor unit
configurations. Main outdoor unit is the unit to which F1‑F2 IN transmission line is
connected. Main, Sub 1 and Sub 2 outdoor units can be identified by field setting
1‑00.
Trigger
Effect
Reset
Transmission abnormality
between outdoor unit
main PCB and inverter
PCB A6P.
Unit will stop operating.
Power reset at outdoor
unit.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Check wiring main PCB and inverter PCB.
2
Check if connector X41A is correctly inserted. See
Possible cause:
Incorrect wiring.
3
Perform a check of the main PCB. See
290].
Possible cause:
Faulty main PCB.
4
Perform a check of the inverter PCB A6P. See
Possible cause:
Faulty inverter PCB A6P.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.51 H7-01-05-09 – Defective fan inverter PCB A4P
Main error code
Sub error code
Unit
H7
01
Main
05
Sub 1
09
Sub 2