2
|
Troubleshooting
Service manual
89
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform a check of the upper heat exchanger gas pipe thermistor. See
348].
Possible cause:
Faulty upper heat exchanger gas pipe thermistor.
2
Perform a check of the main PCB. See
290].
Possible cause:
Faulty main PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.69 J6-11-12-13 – Lower heat exchanger gas pipe thermistor R9T malfunction
Main error code
Sub error code
Unit
J6
11
Main
12
Sub 1
13
Sub 2
INFORMATION
Main, Sub 1 and Sub 2 indications are relevant in multiple outdoor unit
configurations. Main outdoor unit is the unit to which F1‑F2 IN transmission line is
connected. Main, Sub 1 and Sub 2 outdoor units can be identified by field setting
1‑00.
Trigger
Effect
Reset
Lower heat exchanger gas
pipe thermistor R9T
short/open circuit or out
of range.
Unit will stop operating.
Manual reset via user
interface.
Automatic reset when
thermistor read-out is
within range.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform a check of the lower heat exchanger gas pipe thermistor. See
348].
Possible cause:
Faulty lower heat exchanger gas pipe thermistor.
2
Perform a check of the main PCB. See
290].
Possible cause:
Faulty main PCB.