2
|
Troubleshooting
Service manual
92
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform a check of the upper heat exchanger liquid temperature thermistor.
See
348].
Possible cause:
Faulty upper heat exchanger liquid temperature thermistor.
2
Perform a check of the main PCB. See
Possible cause:
Faulty main PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.73 J8-08-09-10 – Lower heat exchanger liquid temperature thermistor R5T abnormality
Main error code
Sub error code
Unit
J8
01
Main
02
Sub 1
03
Sub 2
INFORMATION
Main, Sub 1 and Sub 2 indications are relevant in multiple outdoor unit
configurations. Main outdoor unit is the unit to which F1‑F2 IN transmission line is
connected. Main, Sub 1 and Sub 2 outdoor units can be identified by field setting
1‑00.
Trigger
Effect
Reset
Lower heat exchanger
liquid temperature
thermistor R5T short/
open circuit or out of
range.
Unit will stop operating.
Manual reset via user
interface.
Automatic reset when
thermistor read-out is
within range.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform a check of the lower heat exchanger liquid temperature thermistor.
See
348].
Possible cause:
Faulty lower heat exchanger liquid temperature thermistor.
2
Perform a check of the main PCB. See
Possible cause:
Faulty main PCB.