7
|
Configuration
Installer and user reference guide
89
RYYQ+RYMQ+RXYQ8~20U7Y1B
VRV IV+ heat pump
4P546228-1A – 2019.10
3
Push BS2 18 times.
Result:
Mode 2 setting 18 is addressed:
4
Push BS3 1 time; the value which is returned (depending on the actual field
situation), is the status of the setting. In the case of [2‑18], default value is "0",
which means the function is not active.
Result:
Mode 2 setting 18 is addressed and selected, return value is the
current setting situation.
5
To change the value of the setting, push BS2 till the required value appears on
the 7‑segment display indication. When achieved, define the setting value by
pushing BS3 1 time. To start operation according to the chosen setting,
confirm again by pushing BS3.
6
To leave the monitoring function, push BS1 2 times.
Result:
You will return to the default situation when shipped from factory.
7.2.7 Mode 1: Monitoring settings
[1‑0]
Shows whether the unit you check is a master, slave 1 or slave 2 unit.
Master, slave 1 and slave 2 indications are relevant in multiple outdoor unit system
configurations. The allocation of which outdoor unit is master, slave 1 or slave 2
are decided by the unit's logic.
The master unit should be used to input field settings in mode 2.
[1‑0]
Description
No indication
Undefined situation.
0
Outdoor unit is master unit.
1
Outdoor unit is slave 1 unit.
2
Outdoor unit is slave 2 unit.
[1‑1]
Shows the status of low noise operation.
Low noise operation reduces the sound generated by the unit compared to
nominal operating conditions.
[1‑1]
Description
0
Unit is currently not operating under low noise
restrictions.
1
Unit is currently operating under low noise restrictions.
Low noise operation can be set in mode 2. There are two methods to activate low
noise operation of the outdoor unit system.
▪
The first method is to enable an automatic low noise operation during night time
by field setting. The unit will operate at the selected low noise level during the
selected time frames.
▪
The second method is to enable low noise operation based on an external input.
For this operation an optional accessory is required.
[1‑2]
Shows the status of power consumption limitation operation.
Summary of Contents for VRV IV+
Page 165: ......
Page 166: ......
Page 167: ......
Page 168: ...4P546228 1A 2019 10 Copyright 2018 Daikin Verantwortung für Energie und Umwelt ...