Troubleshooting
Service manual
110
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
Trigger
Effect
Reset
Inverter PCB A6P fails
reading/writing memory
(EEPROM error).
Unit will stop operating.
Manual reset via user
interface.
Power reset at outdoor
unit.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform a check of the inverter PCB A6P. See
274].
Possible cause:
Faulty inverter PCB A6P or non‑compatible inverter PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.96 L1-47-49-51 – Inverter PCB A3P 16 V DC abnormal
Main error code
Sub error code
Unit
L1
47
Main
49
Sub 1
51
Sub 2
INFORMATION
Main, Sub 1 and Sub 2 indications are relevant in multiple outdoor unit
configurations. Main outdoor unit is the unit to which F1‑F2 IN transmission line is
connected. Main, Sub 1 and Sub 2 outdoor units can be identified by field setting
1‑00.
Trigger
Effect
Reset
Main PCB detects voltage/
current errors on output
waveform or current
read-out.
Unit will stop operating.
Manual reset via user
interface.
Power reset at outdoor
unit.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform a check of the main PCB. See
Possible cause:
Faulty main PCB or wrong capacity setting.
2
Perform a check of the inverter PCB A3P. See
274].
Possible cause:
Faulty inverter PCB A3P or non‑compatible inverter PCB.
3
Perform a check of the compressor. See
Possible cause:
Faulty compressor.
Summary of Contents for VRV IV+
Page 473: ......
Page 474: ......