Troubleshooting
Service manual
120
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
2.3.105 L5-14-15-16 – Output overcurrent detection on inverter PCB A6P
Main error code
Sub error code
Unit
L5
14
Main
15
Sub 1
16
Sub 2
INFORMATION
Main, Sub 1 and Sub 2 indications are relevant in multiple outdoor unit
configurations. Main outdoor unit is the unit to which F1‑F2 IN transmission line is
connected. Main, Sub 1 and Sub 2 outdoor units can be identified by field setting
1‑00.
Trigger
Effect
Reset
Inverter PCB A6P detects
overcurrent to power
transistor.
Unit will stop operating.
Manual reset via user
interface.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Check if the power supply is conform with the regulations. See
356].
Possible cause:
▪
Faulty or disturbance of the power supply (imbalance >10%),
▪
Power drop,
▪
Short circuit.
2
Check if the refrigerant circuit is clogged. See
363].
Possible cause:
Clogged refrigerant circuit.
3
Check that all stop valves of the refrigerant circuit are open. See
363].
Possible cause:
Closed stop valve in the refrigerant circuit.
4
Check for the presence of non‑condensables and/or humidity in the
refrigerant circuit. See
Possible cause:
Non‑condensables and/or humidity in the refrigerant circuit.
5
Perform a check of the inverter PCB A6P. See
274].
Possible cause:
Faulty inverter PCB A6P.
6
Perform a check of the compressor M2C. See
Possible cause:
Faulty compressor M2C.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.