2
|
Troubleshooting
Service manual
162
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
6
Set field setting 2‑5 of the outdoor unit to 1 to start the indoor units
connected to that outdoor unit on forced fan operation, see
455]. If any of these indoor units is NOT operating, check the
indoor unit(s) that have power black‑out or malfunctioning PCB. See service
manual of the respective indoor unit for more information.
Possible cause:
Power black‑out or malfunctioning PCB on indoor unit(s).
7
Check indoor units for error.
8
Refer to indoor unit error codes and indoor unit manuals to troubleshoot.
Possible cause:
Indoor unit on error.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.157 U4-15 – Unable to start test run
Trigger
Effect
Reset
Main PCB detects
malfunction on indoor
unit(s).
Test run will NOT start.
Perform test run.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Set field setting 2‑5 of the outdoor unit to 1 to start the indoor units
connected to that outdoor unit on forced fan operation, see
455]. If any of these indoor units is NOT operating, check the
indoor unit(s) that have power black‑out or malfunctioning PCB. See service
manual of the respective indoor unit for more information.
Possible cause:
Power black‑out or malfunctioning PCB on indoor unit(s).
2
Check field setting 1‑10 to count the indoor units, see
455]. If less indoor units detected than it should be, check the
indoor unit(s) that have power black‑out or malfunctioning PCB. See service
manual of the respective indoor unit for more information.
Possible cause:
Power black‑out or malfunctioning PCB on indoor unit(s).
3
Perform a check of the main PCB. See
Possible cause:
Faulty main PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.158 U7-01 – Transmission abnormality between systems - DTA104A61,62 error
Trigger
Effect
Reset
Communication problem
between systems.
Unit will stop operating.
Auto reset when
communication is normal.