2
|
Troubleshooting
Service manual
17
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
Action
Result
Display
Make sure the 7-segment
display indication is as
during normal operation.
To enter “Mode 1”, push
the (BS1) button one time
Mode 1 is accessed.
Push the (BS2) button as
many times as the setting
you want to go to.
The setting is accessed
(e.g. 17, Error code last
forced off)
Press the RETURN (BS3)
Button.
Malfunction/Retry item
will appear on display.
Press the SET (BS2)
Button.
Detailed Malfunction/
Retry sub-code will
appear on display.
Press SET (BS2) once
again to return to main
Malfunction/Retry
display.
Main Malfunction/Retry
item will appear on
display.
Press the RETURN (BS3)
Button to return to Home
Screen for “Monitoring
Mode”.
Home Screen for
“Monitoring Mode” will
appear on display.
Press the MODE (BS1)
Button to return to
“Normal Mode”.
Back in normal mode.
2.2.3 Via the wired remote control BRC1E
INFORMATION
Images are in English and for reference ONLY. For more details on the BRC1E please
refer to the user manual.
To retrieve the error code
In case of an error or warning, the operation lamp on the ON/OFF button blinks
and an error message or warning is displayed at the bottom of the screen.
a
b
c
a
Operation lamp on the ON/OFF button
b
Error message