3
|
Components
Service manual
238
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
3
Check that pins 1 and 4 on connector X101A are bridged.
Result:
If the pins are NOT bridged, install the bridge.
a
a
Connector X101A
4
Check the wiring from pins 2 and 3 of connector X101A to the current sensor.
5
Disconnect the current sensor connector from the connector X101A on the
main PCB and measure the resistance between pins 2 and 3 of the current
sensor connector.
Result:
The measured value MUST be 45~50 Ω.
Is the measured resistance correct?
Action
Yes
Return to the troubleshooting of the
specific error and continue with the
next procedure.
No
Replace the current sensor, see
238].
3.5.2 Repair procedures
To remove the current sensor
Prerequisite:
Stop the unit operation via the central controller.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
315].
1
Disconnect the current sensor connector from the main PCB.
a
b
c
b
b
d
e
e
a
Current sensor