3
|
Components
Service manual
259
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
4
Fix the expansion valve coil harness using new tie straps.
5
Install the insulation cap on the expansion valve motor (if applicable).
Is the problem solved?
Action
Yes
No further actions required.
No
Return to
252] of the expansion
valve and continue with the next
procedure.
3.8 Fan inverter PCB
3.8.1 Single fan outdoor unit
Checking procedures
INFORMATION
It is recommended to perform the checks in the listed order.
To perform a power check of the fan inverter PCB
Prerequisite:
Stop the unit operation via the central controller.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
Prerequisite:
315].
1
Turn ON the power of the unit.
2
Measure the voltage between pins 1 and 3 of connector X5A The measured
voltage MUST be 18 V DC.
a
b
a
Pin 1
b
Pin 3
Is the measured voltage on the PCB
correct?
Action
Yes
Return to
259] of the PCB and
continue with the next procedure.
No
Continue with the next step.
3
Measure the output voltage voltage on connector X601A on the inverter PCB.
Result:
The measured voltage MUST be 18 V DC.