Troubleshooting
Service manual
28
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
Possible cause:
Refrigerant overcharge.
6
Check for the presence of non‑condensables and/or humidity in the
refrigerant circuit. See
Possible cause:
Non‑condensables and/or humidity in the refrigerant circuit.
7
Check if the refrigerant circuit is clogged. See
363].
Possible cause:
Clogged refrigerant circuit.
8
Perform a check of the condenser side expansion valve. See
244].
Possible cause:
Faulty condenser side expansion valve.
9
Perform a check of the main PCB. See
Possible cause:
Faulty main PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.8 E3-07 – High pressure switch reset error
Trigger
Effect
Reset
High pressure switch did
not reset and it stays
activated.
Unit will stop operating.
If field setting 2-15=1
(default): Via the indoor
unit remote controller,
cycle OFF & ON.
If field setting 2-15=0:
Press BS3 on main PCB on
outdoor unit, and then via
indoor unit remote
controller, cycle OFF &
ON.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Check that all stop valves of the refrigerant circuit are open. See
363].
Possible cause:
Closed stop valve in the refrigerant circuit.
2
Perform a check of the high pressure switch. See
Possible cause:
Faulty high pressure switch.
3
Perform a check of the main PCB. See
Possible cause:
Faulty main PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.