3.12.2 Repair procedures
To correct the wiring from the main power supply terminal to the noise filter PCB
Prerequisite:
Stop the unit operation via the central controller.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
1
315].
2
Make sure that all wires are firmly and correctly connected, see
3
Check the continuity of all wires.
4
Replace any damaged or broken wires.
Is the problem solved?
Action
Yes
No further actions required.
No
Return to
298] of the noise filter
PCB and continue with the next
procedure.
To remove the noise filter PCB
Prerequisite:
Stop the unit operation via the central controller.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
1
315].
2
Disconnect all the wires of the noise filter PCB.
INFORMATION
The connectors on the PCB can be screw- or Faston-type, depending on the model.
b
b
a
b
b
b
b
a
a
a
a
a
a
a
a
Connector
b
PCB supports
3
Carefully pull the PCB at the side and unlatch the PCB supports one by one
using a small pair of pliers.
4
To install the new noise filter PCB, see
301].