3
|
Components
Service manual
302
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
To install the noise filter PCB
1
Install the noise filter PCB on its correct location.
2
Latch the PCB supports to fix the noise filter PCB.
b
b
a
b
b
b
b
a
a
a
a
a
a
a
a
Connector
b
PCB supports
3
Connect all the wires to the connectors of the noise filter PCB.
INFORMATION
The connectors on the PCB can be screw- or Faston-type, depending on the model.
Is the problem solved?
Action
Yes
No further actions required.
No
PCB and continue with the next
procedure.
3.13 Oil return valve
3.13.1 Checking procedures
INFORMATION
It is recommended to perform the checks in the listed order.
To perform a mechanical check of the oil return valve
Prerequisite:
Stop the unit operation via the central controller.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
315].
1
Verify that the screw is firmly fixing the coil to the valve body.
2
Check if any damage or burst is present.
Is the oil return valve coil firmly fixed
and not visually damaged?
Action
Yes
Perform an electrical check of the oil
return valve, see
No
Fix or replace the oil return valve coil,
see