3
|
Components
Service manual
313
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
INFORMATION
Winding resistance values above are given for reference. You should NOT be reading
a value in kΩ or a short‑circuit. Make sure that the propeller fan blade does NOT
rotate, as this could affect resistance measurements.
9
Measure the insulation resistance for the motor terminals. Measurements
between each phase and ground must be >1°MΩ.
Are the measured resistance values
correct?
Action
Yes
Perform a check of the fan inverter PCB,
see
265].
No
Replace the DC fan motor assembly, see
Problem solved?
After all checking procedures listed above have been performed:
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
Repair procedures
To remove the propeller fan blade assembly
Prerequisite:
Stop the unit operation via the central controller.
Prerequisite:
Turn OFF the respective circuit breaker.
1
Remove the required plate work, see
2
Loosen and remove the screw using an Allen key.
3
Remove the axle cover.
4
Pull the propeller fan blade from the fan motor axle.
c
b
d
a
e
a
Screw
b
Allen key
c
Axle cover
d
Propeller fan blade assembly
e
Pulley remover