3
|
Components
Service manual
315
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
8
Install the propeller fan blade assembly, see
313].
9
Install the plate work of the outdoor unit, see
315].
To install the propeller fan blade assembly
1
Install the propeller fan blade assembly on the DC fan motor assembly.
CAUTION
Do NOT install a damaged propeller fan blade assembly.
2
Install the axle cover.
3
Install and tighten the screw using an Allen key to fix the propeller fan blade
assembly.
c
b
d
a
e
a
Screw
b
Allen key
c
Axle cover
d
Propeller fan blade assembly
Is the problem solved?
Action
Yes
No further actions required.
No
Return to
311] of the outdoor unit
fan motor and continue with the next
procedure.
3.15 Plate work
3.15.1 To access the switch box on single fan units
Prerequisite:
Stop the unit operation via the central controller.
Prerequisite:
Turn OFF the respective circuit breaker.
1
Remove the required plate work, see
DANGER: RISK OF ELECTROCUTION
Confirm the rectifier voltage is below 10 V DC before proceeding, see
356].