The measured voltage is inside the
expected range?
Action
Yes
Refrigerant pressure sensor is OK.
Return to the troubleshooting of the
specific error and continue with the
next procedure.
No
Continue with the next step.
6
Unplug the refrigerant pressure sensor connector X32A and measure the
voltage (power supply) between pins 3–4 on main PCB.
Result:
The measured voltage MUST be +5 V DC.
Is the measured v5 V DC?
Then
Yes
Replace the refrigerant pressure sensor,
see
No
Perform a check of the main PCB, see
3.17.2 Repair procedures
To remove the refrigerant pressure sensor
Prerequisite:
Stop the unit operation via the central controller.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
315].
Prerequisite:
Recuperate the refrigerant from the refrigerant circuit, see
368].
Prerequisite:
If needed, remove any parts or insulation to create more space for
the removal.
1
Cut all tie straps that fix the refrigerant pressure sensor harness.
2
Disconnect the refrigerant pressure sensor connector from the PCB.
3
Cut the refrigerant pressure sensor pipe using a pipe cutter.
a
b
a
Refrigerant pressure sensor
b
Refrigerant pressure sensor pipe
4
Remove the refrigerant pressure sensor.
5
Supply nitrogen to the refrigerant circuit. The nitrogen pressure MUST NOT
exceed 0.02 MPa.
6
Heat the end of the refrigerant pressure sensor pipe using an oxygen
acetylene torch and remove the refrigerant pressure sensor pipe end.