2
|
Troubleshooting
Service manual
44
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
Possible cause:
▪
Faulty or disturbance of the power supply (imbalance >10%),
▪
Power drop,
▪
Short circuit.
8
Perform a power reset. If the error disappears and is raised again after a
while, check for the presence of an external source causing electrical noise.
See
372].
Possible cause:
External source may cause interference.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.24 E9-03-06-09 – Electronic expansion valve Y2E malfunction
Main error code
Sub error code
Unit
E9
03
Main
06
Sub 1
09
Sub 2
INFORMATION
Main, Sub 1 and Sub 2 indications are relevant in multiple outdoor unit
configurations. Main outdoor unit is the unit to which F1‑F2 IN transmission line is
connected. Main, Sub 1 and Sub 2 outdoor units can be identified by field setting
1‑00.
Trigger
Effect
Reset
Subcool expansion valve
Y2E malfunction.
Unit will stop operating.
Power reset at outdoor
unit.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
INFORMATION
When the power is switched ON, the outdoor unit main PCB checks all expansion
valve coil windings by current check.
1
Perform a check of the main PCB. See
Possible cause:
Faulty main PCB.
2
Perform a check of the subcool expansion valve. See
244].
Possible cause:
Faulty subcool expansion valve.
3
Perform
a
check
of
all
refrigerant
side
thermistors.
See
Possible cause:
Faulty refrigerant side thermistor(s).