6
|
Technical data
Service manual
449
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
6.6 Safety devices
Wiring
symbol
Component
Description
Trigger
Error
Action type
T1A
Current sensor
Earth leakage
protection
T1A > 75 mA (± 25%)
E2
Drop control
S1PH,
S2PH
High pressure
switch
High pressure
protection
High pressure >4.0 MPa (+0.00,
-0.15)
Reset: high pressure <3.0 MPa
±0.15
E3
Forced stop
S1NPH
High pressure
sensor
High pressure
protection
High pressure >3.72 MPa
Retry 3 times in 40 minutes
E3
Drop control
High pressure >3.55 MPa in
cooling mode
Reset: High pressure <3.04 MPa
Drop control
High pressure >3.04 MPa in
cooling mode
Reset: High pressure <2.89 MPa
Drop control
High pressure >4.15 MPa (means
high pressure switch failed to
open)
JA
Forced stop
S1NPL
Low pressure
sensor
Low pressure
protection
Low pressure <0.07 MPa
Retry 3 times in 60 minutes
E4
Drop control
Low pressure <0.35 MPa in cooling
mode
Reset: Low pressure >0.4 MPa
Drop control
Low pressure <0.17 MPa in
heating mode
Reset: Low pressure >0.23 MPa
Drop control
Low pressure <0.07 MPa
4
th
retry in 60 minutes
E4
Forced stop
M1C,
M2C
Compressor
JT16KBVDYR@S
Current protection Current >28 A
Drop control
M1C,
M2C
Compressor
JT16KBVDYR@S
Current protection When current >28 A, three times
in 60 minutes
L8
Forced stop
M1C,
M2C
Compressor
JT1GUVDYR@BA
Current protection When current >17 A
Drop control
M1C,
M2C
Compressor
JT1GUVDYR@BA
Current protection When current >17.6 A, three times
in 60 minutes
L8
Forced stop
R21T,
R22T
Discharge pipe
thermistor
Overheat
protection
Temperature >135˚C for 2 times
within 100 minutes
Reset: Temperature <95˚C
F3
Forced stop
Temperature >108˚C
Reset: Temperature <95˚C
Drop control
R15T
Compressor body
thermistor
Overheat
protection
Temperature >108˚C
Drop control