2
|
Troubleshooting
Service manual
85
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform
a
check
of
the
discharge
pipe
thermistor.
See
348].
Possible cause:
Faulty discharge pipe thermistor or connector fault.
2
Perform a check of the lower heat exchanger expansion valve. See
244].
Possible cause:
Faulty lower heat exchanger expansion valve.
3
Perform a check of the upper heat exchanger expansion valve. See
244].
Possible cause:
Faulty upper heat exchanger expansion valve.
4
Perform a check of the subcool expansion valve. See
Possible cause:
Faulty subcool expansion valve.
5
Perform a check of the expansion valve(s) of the indoor unit(s). See service
manual of the respective indoor unit(s) for more information.
Possible cause:
Faulty indoor unit expansion valve.
6
Perform a check of the main PCB. See
290].
Possible cause:
Faulty main PCB.
7
Check if the refrigerant circuit is correctly charged. See
Possible cause:
Refrigerant shortage.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.64 J3-59-60-61 – Discharge thermistor crosswired
Main error code
Sub error code
Unit
J3
59
Main
60
Sub 1
61
Sub 2
INFORMATION
Main, Sub 1 and Sub 2 indications are relevant in multiple outdoor unit
configurations. Main outdoor unit is the unit to which F1‑F2 IN transmission line is
connected. Main, Sub 1 and Sub 2 outdoor units can be identified by field setting
1‑00.