Troubleshooting
Si-95
112
Troubleshooting Inverter K Series
2.36
Malfunction of System, Refrigerant System Address Undefined
Remote Controller
Display
UUU
UHHHH
Supposed Causes
■
Improper connection of transmission wiring between indoor-outdoor unit or outdoor-outdoor unit
■
Defect of indoor unit PC board
■
Defect of outdoor unit PC board (A1P)
Troubleshooting
(VF062)
NO
YES
YES
After fixing incorrect wiring, push
and hold the RESET button on the
outdoor unit PC board for 5
seconds.
Normal
NO
Is electricity
being introduce for
the first time after installation
or after an indoor or outdoor
unit PC board has
been replaced?
Is
indoor - outdoor and
outdoor - outdoor unit
transmission wiring
normal?
YES
Normal
NO
Does a malfunction occur?
NO
Does
a "UH" malfunction occur for
all indoor units in
the system?
YES
NO
Does
a malfunction
occur even after 12
minutes elapses from the time
when electricity is introduced
to indoor and outdoor
units?
YES
Replace indoor unit PC board.
Replace outdoor unit PC board
(A1P).
Hold the RESET button on the
outdoor unit PC board for 5
seconds
∗
The unit will not run for up to 12
minutes.
SI-95.BOOK Page 112 Friday, March 31, 2000 10:59 AM