Si-95
Outline
General Information Inverter K Series
3
1.2
Allowed Range of Indoor Unit and BS Unit Connection
■
Arrange systems to conform below conditions referring to above diagram.
Indoor unit
( Cooling
only unit )
( Cooling
only unit )
BS unit
Range A
Range B
Range C
Range C
Range C
Range C
Range
Item
Model of outdoor
unit and BS unit
Total capacity of
connectable indoor
units
Max. number of
connectable indoor
units
Range A Total indoor unit capacity
RSEY8KLY1
11.2 to 29.1kW
13 units
RSEY10KLY1
14 to 36.4kW
16 units
Range B Total indoor unit capacity
allowed for simultaneous
cooling/heating operations
RSEY8KLY1
11.2kW or more
13 units
RSEY10KLY1
14kW or more
16 units
Range C Total indoor unit capacity
allowed for connection to BS unit
BSV100KLV1
less than 11.2kW
5 units or less
BSV160KLV1
11.2 to 18kW
6 units or less
BSV250KLV1
18 to 28kW
16 units or less
SI-95.BOOK Page 3 Friday, March 31, 2000 10:59 AM