Troubleshooting (Inverter)
Si-95
120
Troubleshooting Inverter K Series
4.6
Power Supply Insufficient or Instantaneous Failure
Remote Controller
Display
UUU
U2222
Supposed Causes
■
Power supply insufficient
■
Instantaneous power failure
■
Lack of phase
■
Defect of inverter unit
■
Defect of outdoor PC board
■
Defect of K1M.
■
Main circuit wiring defect
Troubleshooting
(VF068)
Replace K1M.
NO
Turn on again.
Replace the outdoor unit PC board.
YES
Turn K1M ON.
YES
NO
Is 220 ~ 240 V of power
reaching the K1M
coil?
Is 220 ~ 240 V at
the connector of X1A.
Replace the inverter unit.
Replace the inverter unit.
YES
NO
YES
Does
the voltage
between terminals P
and N gradually rise to 339
VDC (Y1) after
turning on?
"U2" blinks again.
Monitor field power supply.
The voltage
between the P and N
terminals is 320 VDC (Y1)
or more when the
compressor
is running.
NO
NO
Is 220 ~ 240 V of outdoor
PC board side?
Check
the transmission
wiring between the outdoor
unit PC board and
inverter unit.
YES