Functions Inverter K Series
Operation Contents
Step 1
→
Discharge defrost
k = kg/cm
2
Compressor
86Hz + OFF
EEV
2000pls
Outdoor Unit Fan
OFF + OFF
Outdoor Unit Heat Exchanger
Condenser
4 Way Valve
OFF
Injection 1
Td Protection Control
Injection 2
OFF
Hot Gas
ON
3 Minutes Elapsed
Step 2
→
Suction defrost
Compressor
86Hz + OFF
EEV
2000pls
Outdoor Unit Fan
OFF + OFF
Outdoor Unit Heat Exchanger
Condenser
4 Way Valve
OFF
Injection 1
Td Protection Control
Injection 2
Td Protection Control
Hot Gas
ON
Conclution of Defrost Completion
Condition
or
All of R2-1T, R2-2T
≥
12.5ºC
Pc > 20.5k
10 Minutes Elapsed Since
Defrost Operation Start
Step 3
→
BS solenoid valve changeover
Compressor
38Hz + OFF
EEV
2000pls
Outdoor Unit Fan
OFF + OFF
Outdoor Unit Heat Exchanger
Condenser
4 Way Valve
OFF
Injection 1
Td Protection Control
Injection 2
OFF
Hot Gas
ON
40 Seconds Elapsed
Step 4
→
Refrigerant is discharged from accumulator
Compressor
76Hz + OFF
EEV
Limit of EV Opening
Outdoor Unit Fan
H + ON
Outdoor Unit Heat Exchanger
Evaporator
4 Way Valve
ON
Injection 1
Td Protection Control
Injection 2
OFF
Hot Gas
Low Pressure Protection Control
or
5 Minutes Elapsed
Pc > 14k
R5T > Te + 10ºC
Normal Control
∗
Pc = Condensing Pressure
Preparation
for Defrost
Upper Limit Frequency
Limited to 38Hz + ON
1 Minute
Elapses
(VF015)