Test Operation
SiE-05C
102
Test Operation Inverter K Series
Control Wiring
Connection
Example
(Indoor units in same system shown in the following examples.)
1. series wiring
2. Bus wiring (can be branched in max. 16 locations)
Example showing 3 branches
3. Star wiring (can be branched in max. 16 locations)
Example showing 3 branches
Notes
1. Cannot be branched again after being branched once.
2. Use a junction terminal block if branching 3 or more control wires from the same terminal block.
3. Do not connect transmission wiring between indoor and outdoor units of different refrigerant circuits.
SI-05C.BOOK Page 102 Monday, November 6, 2000 4:13 PM
Все каталоги и инструкции здесь:
http
:
//splitoff.ru/tehn-doc.html