Test Operation
SiE-05C
106
Test Operation Inverter K Series
A Group of Indoor
Units
1. 1 indoor unit with no remote controller
NOTE:
If not using remote controllers, use in combination with central remote controller.
2. 1 indoor unit controlled by either 1 or 2 remote controllers
3. Max. 16 indoor units group-controlled by either 1 or 2 remote controllers
1.20.2 Wiring for Transmission
Wiring Outline
Wiring specifications
Connection
Example of Wiring
for Transmission
(1)series wiring, (2)bus type wiring and (3)star type wiring are the same as with a central remote
controller.
Power supply wiring
2 mm
²
Wiring for transmission
0.75 ~ 1.25 mm
²
sheathed vinyl cord or cable (double core); max. extension
1000 m (total wiring length 2000 m)
Power supply switch
10A
SI-05C.BOOK Page 106 Monday, November 6, 2000 4:13 PM