Test Operation
SiE-05C
112
Test Operation Inverter K Series
1.22
Combining Different Types of Centralized Control Devices
<DCS302A51 · DCS301A51 · DST301A51>
<DCS302B61 · DCS301B61 · DST301B61>
In addition to using optional controllers for centralized control independently, you also combine and
connect a schedule timer and unified ON/OFF controller with a central remote controller. By designing with
components, you can construct the best central remote control system for your purpose and scale.
1.22.1 Example of DCS302A51 / DCS301A51/ DST301A51 Systems
Unified ON/OFF controller
Unified ON/OFF controllers are connected in accordance with the number of indoor units. A single line
network can contain up to 16 groups of four units each.
Central remote controller plus unified ON/OFF controller
Combines the functionality of a central remote controller with the operability of a unified ON/OFF controller.
Enables central control of up to 64 groups of indoor units.
Schedule timer plus central remote controller
Allows you to set up to eight weekly schedules for turning units ON/OFF twice each day. Enables
scheduled operation of up to 64 groups of indoor units individually or by zone.
Schedule timer plus unified ON/OFF controller
Allows you to set the time for turning units ON/OFF twice each day.
Enables unified scheduled operation of up to 64 groups of indoor units.
SI-05C.BOOK Page 112 Monday, November 6, 2000 4:13 PM