SiE-05C
Operation Flowcharts
Troubleshooting Inverter K Series
121
Program dry operation
Program dry dieplay
Thermostat status?
Fan MF : 6 minutes stopped
then L operation
Electronic expansion valve Y1E
closed
Drain-up kit M1P : Off after 5
minutes residual operation
Fan MF : operation: L
Electronic expansion valve Y1E
degree of super heat control
A
(Option)
∗
7
∗
8
(VF023)
ON
OFF
∗
7 Programmed dry display
Does not display preset temperature and air flow settings of the controller.
∗
8 Thermostat status
Preset temperature during programmed dry operation
Fan in operation
Swing flap
Air flow direction setting
Swing flap?
Fan MF: Operating at set air flow
rate
Electronic expansion valve Y1E
closed
Drain-up kit (M1P): OFF
Auxiliary electric heater (52H): OFF
Humidifier (Hu): OFF
Electric dust collector: ON
A
∗
10
∗
11
∗
9
No
YES
Opetion
(VF024)
∗
9
Fan operation
When fan operation has been selected using the remote controller, operation is turned OFF by
thermostat when temperature control operation has been selected.
∗
10 Air flow direction setting
If fan operation is selected with the remote controller, air discharge is 100% horizontal during
heating.
∗
11 Fan
If fan operation is selected with the remote controller, LL speed operation is carried out during
heating.
SI-05C.BOOK Page 121 Monday, November 6, 2000 4:13 PM