SiE-05C
Troubleshooting
Troubleshooting Inverter K Series
135
3.6
Indoor Unit: Malfunction of Moving Part of Electronic Expansion Valve (Y1E)
Remote Controller
Display
AAA
A9999
Supposed Causes
Malfunction of moving part of electronic expansion valve
Defect of indoor unit PC board
Defect of connecting cable
Troubleshooting
∗
1: Coil check method for the moving part of the electronic expansion valve
(Normal)
: Continuity
x: No continuity
(VF033)
After connecting, turn the power supply
off and then back on.
Replace the moving part of the
electronic expansion valve.
YES
YES
NO
NO
Replace the connecting cable.
If you turn the power supply off and
turn on again, and it still does not help,
replace the indoor unit PC board.
NO
YES
The electronic
expansion valve is connected
to X7A of the indoor unit
PC board.
Normal
when coil check (
∗
1) of
the moving part of the electronic
expansion valve
is checked.
The connecting
cable is short-circuited or
disconnected.
Pin No.
1. White
2. Yellow
3. Orange
4. Blue
5. Red
6. Brown
1. White
x
Approx. 300
Ω
x
Approx. 150
Ω
x
2. Yellow
x
Approx. 300
Ω
x
Approx. 150
Ω
3. Orange
x
Approx. 150
Ω
x
4. Blue
x
Approx. 150
Ω
5. Red
x
6. Brown
SI-05C.BOOK Page 135 Monday, November 6, 2000 4:13 PM