Troubleshooting
SiE-05C
138
Troubleshooting Inverter K Series
3.11
Indoor Unit: Malfunction of Thermistor (R1T) for Air Inlet
Remote Controller
Display
CCCC999
9
Supposed Causes
Defect of indoor unit thermistor (R1T) for air inlet
Defect of indoor unit PC board
Troubleshooting
3.12
Indoor Unit: Malfunction of Thermostat Sensor in Remote Controller
Remote Controller
Display
CCCCJJJJ
Supposed Causes
Defect of remote controller thermistor
Defect of remote controller PC board
Troubleshooting
Replace the indoor unit PC board.
Connect the thermistor and turn on
again.
NO
NO
Replace the thermistor (R1T).
YES
YES
Connector
is connected to X13A of
the indoor unit PC
board.
Resistance
is normal when
measured after
disconnecting the thermistor
(R1T) from the indoor unit
PC board. (7.2k
Ω
~
112k
Ω
)
(VF038)
(VF039)
The remote
controller thermistor
or remote controller PC
board is defective.
Replace the remote controller.
SI-05C.BOOK Page 138 Monday, November 6, 2000 4:13 PM