Troubleshooting
SiE-05C
148
Troubleshooting Inverter K Series
3.25
Outdoor Unit: Malfunction of Oil Temperature Thermistor (R5T)
Remote Controller
Display
JJJJHHH
H
Supposed Causes
Defect of oil temperature thermistor (R5T)
Defect of outdoor unit PC board (A1P)
Troubleshooting
(VF051)
The outdoor
unit type is 8 K or 10K.
Is the connector
is connected to X15A of
the outdoor PC board
(A1P)?
Resistance
is normal when
measured with thermistor
(R5T) disconnected from the
outdoor unit PC board.
(0.6 k
Ω
~360 k
Ω
)
Replace outdoor unit PC board (A1P).
Connect the thermistor and and turn on
again.
Replace thermistor (R5T).
Replace outdoor unit PC board (A1P).
YES
YES
YES
NO
NO
NO
SI-05C.BOOK Page 148 Monday, November 6, 2000 4:13 PM