SiE-05C
Troubleshooting
Troubleshooting Inverter K Series
149
3.26
Low Pressure Drop Due to Refrigerant Shortage or Electronic Expansion
Valve Failure
Remote Controller
Display
UUU
U000
0
Supposed Causes
Out of gas or refrigerant system clogging (incorrect piping)
Defect of pressure sensor
Defect of outdoor unit PC board
Troubleshooting
(VF052)
The suction
pipe temperature minus
coil temperature is 20 ˚C
or higher.
Resistance
is normal when
measured with the suction
pipe thermistor (R4T) and
coil thermistor (R2T)
disconnected
from the outdoor
unit PC
board.
Out of gas or refrigerant system is
clogged. Requires check of
refrigerant system.
Replace the thermistor.
Replace the outdoor unit PC
board.
YES
NO
NO
Out of gas or refrigerant system is
clogged. Requires check of
refrigerant system.
Replace outdoor unit PC board.
YES
YES
NO
Cooling
Low pressure
is 1.0 kg/cm² (0.098 MPa) or
less.
The voltage
of X21A pins (2)
and (3) on both sides of
outdoor unit PC board (A1P) is
0.8 VDC or less.
(Pressure sensor
output
voltage)
NO
NO
YES
YES
Replace pressure sensor.
SI-05C.BOOK Page 149 Monday, November 6, 2000 4:13 PM