Troubleshooting
SiE-05C
156
Troubleshooting Inverter K Series
3.33
Excessive Number of Indoor Units
Remote Controller
Display
UUU
UAAA
A
Supposed Causes
Excess of connected indoor units
Defect of outdoor unit PC board (A1P)
Troubleshooting
The number of indoor units that can be connected to a single outdoor unit system depends on the type of
outdoor unit.
RSXY 5K : Max. 8 units
RSXY 8K : Max. 13 units
RSXY10K : Max. 16 units
3.34
Address Duplication of Central Remote Controller
Remote Controller
Display
UUU
UCCCC
Supposed Causes
Address duplication of central remote controller
Defect of indoor unit PC board
Troubleshooting
(VF059)
The total
of indoor units
displaying "UA" and indoor
units connected to the same
refrigerant system is
24 units or
less.
Replace outdoor unit PC board (A1P).
Normal
NO
NO
There are too many indoor units within
the same refrigerant system.
Push and hold the RESET
button on the outdoor unit PC
board for 5 seconds.
YES
YES
Does a malfunction occur?
(VF060)
Replace indoor unit PC board.
Address duplication of central remote
controller
The setting must be changed so that
the central remote control address is
not duplicated.
YES
NO
Optional
controllers for
centralized control are
connected to the
indoor unit.
SI-05C.BOOK Page 156 Monday, November 6, 2000 4:13 PM