Troubleshooting
SiE-05C
158
Troubleshooting Inverter K Series
3.36
Malfunction of System, Refrigerant System Address Undefined
Remote Controller
Display
UUU
UHHH
H
Supposed Causes
Improper connection of transmission wiring between outdoor unit and outdoor unit outside control
adaptor
Defect of indoor unit PC board
Defect of outdoor unit PC board (A1P)
Troubleshooting
(VF062)
NO
YES
YES
After fixing incorrect wiring, push
and hold the RESET button on the
outdoor unit PC board for 5
seconds.
Normal
NO
Is electricity
being introduce for
the first time after installation
or after an indoor or outdoor
unit PC board has
been replaced?
Is
indoor - outdoor and
outdoor - outdoor unit
transmission wiring
normal?
YES
Normal
NO
Does a malfunction occur?
NO
Does
a "UH" malfunction occur for
all indoor units in
the system?
YES
NO
Does
a malfunction
occur even after 12
minutes elapses from the time
when electricity is introduced
to indoor and outdoor
units?
YES
Replace indoor unit PC board.
Replace outdoor unit PC board
(A1P).
After fixing incorrect wiring,
push and hold the RESET
button on the outdoor unit PC
board for 5 seconds Replace
whichever is defective.
∗
The unit will not run for up to 12
minutes.
SI-05C.BOOK Page 158 Monday, November 6, 2000 4:13 PM