SiE-05C
Outline of Control
Functions PLUS Series
221
4.1.2
Cooling Start Following Layup
When starting for the first time after turning on the power, temporarily starts all outdoor units in order to
discharge refrigerant from the low pressure line and accumulator when outdoor temperature is low.
Outdoor Unit Operation During Cooling Accumulation Start
∗
EEV : Herein after we indicate EEV for Electronic expansion valve.
<In Case of Cooling
Only System>
Outdoor unit and function unit operation during cooling accumulation start
Soft start
1 minute elapses
Liquid discharged
from
accumulators of
all outdoor units
Liquid discharged
from
accumulators of
all outdoor units
• 4 minutes elapse
or
• Low pressure < 1k
or
• 3 minutes elapse
• Low pressure < 1k
Normal control
(k:kg/cm
2
)
(VF101)
1
2
3
1
2
3 (Initial settings)
INV
outdoor
unit
STD
outdoor
unit 1
STD
outdoor
unit 2
INV
outdoor
unit
STD
outdoor
unit 1
STD
outdoor
unit 2
INV
outdoor
unit
STD
outdoor
unit 1
STD
outdoor
unit 2
Compressor
48+OFF
ON+OFF
ON+OFF
48+OFF
ON+OFF
ON+OFF
48+OFF
OFF
OFF
Outdoor fan
Control by high pressure
H+ON
Outdoor EEV
2000PLS
2000PLS
2000PLS
2000PLS
2000PLS
2000PLS
2000PLS
0PLS
0PLS
Hot gas bypass
ON
ON
ON
ON
OFF
OFF
ON
OFF
OFF
Hot gas bypass
for equalizing
pressure
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Injection
No1
Td safety
control
Td safety
control
Td safety
control
Td safety
control
Td safety
control
Td safety
control
Td safety
control
OFF
OFF
No2
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Oil contral
solenoid valve
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
1
2
3 (Initial settings)
INV
outdoor
unit
STD
outdoor
unit 1
STD
outdoor
unit 2
INV
outdoor
unit
STD
outdoor
unit 1
STD
outdoor
unit 2
INV
outdoor
unit
STD
outdoor
unit 1
STD
outdoor
unit 2
Compressor
48 + OFF
ON + OFF ON + OFF
48 + OFF
ON + OFF ON + OFF
48 + OFF
OFF
OFF
Outdoor fan
Control by high pressure
H ## ON
Hot gas bypass
for equalizing
pressure
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Injection
No.1
Td safety
control
Td safety
control
Td safety
control
Td safety
control
Td safety
control
Td safety
control
Td safety
control
OFF
OFF
No.2
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Oil contral
solenoid valve
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Function unit’s
solenoid valve
Y5-ON
Y6-ON
Y7-ON
Y5-ON
Y6-OFF
Y7-OFF
Y5-ON
Y6-OFF
Y7-OFF
SI-05C.BOOK Page 221 Monday, November 6, 2000 4:13 PM