4.10
Discharge Temperature Protection Control
In order to prevent deterioration of refrigeration oil due to rising discharge temperature, temperature is kept
from rising by reduction of compressor frequency or injection cooling at the following stages when
temperature falls below the reference values.
4.10.1 Both Inverter and Standard Outdoor Units
(k:kg/cm
²
)
When Cooling/Heating
Discharge temp.
thermostat
≥
135˚C
Stop due to
F3 malfunction
Cancel conditions
Tdi or Tds < 115˚C
Cancel conditions
Td
≤
95˚C
Up to 2 times within 100 minutes
Discharge temp. thermostat
≥
130˚C
Forced OFF by thermostat
Cancel conditions
Restart standby
Discharge temp. thermostat
≥
95˚C
Frequency reduction
(every 3 minutes)
2 minutes following 1st compressor
start for each unit
No.1 compressor discharge temp.
> 110˚C
or
No.1 compressor superheating temp.
> 55˚C
Injection ON
2 minutes following
oil return and defrost
completion
Injection ON
Cancel conditions
2 minutes elapse
LP < 3.0 (Te < -6.8˚C)
&
Upper flow side comp.
discharge temp. > 90˚C
Injection ON
LP < 2.0 (Te < -15.1˚C)
&
Upper flow side comp.
discharge temp. > 90˚C
Injection ON
Injection ON
Injection ON
During oil return and defrost
preparation only
Discharge superheating temp.
> 35˚C
Discharge superheating temp.
> 15˚C
Oil temp. > 65˚C
(1) No.1 compressor discharge temp. < 90˚C
&
No.1 compressor discharge superheating
temp. < 35˚C
Oil temp. < 55˚C
(2) Upper flow side comp. discharge temp.
below 105˚C
&
Upper flow side comp. discharge
superheating temp.< 50˚C
Oil temp. < Te + 10˚C
(3) Upper flow side comp. discharge superheating
temp. < 15˚C
(4) LP > 4.0 (Te > - 0.4˚C)
or
Upper flow side comp. discharge temp. < 70˚C
(5) LP > 4.0 (Te > - 10.7˚C)
or
Upper flow side comp. discharge temp. < 80˚C
When cooling
When heating
Injection cancel conditions
Injection is canceled if any of the following five conditions are met.
Cancel conditions
No.1 compressor discharge
superheat temp. < 15˚C
or
2 minutes elapse after compressor
start
(VF119)