Outline of Control
SiE-05C
240
Functions PLUS Series
4.15
Low Noise and Demand Control
4.15.1 Low Noise Control
When the outdoor unit operating sound can cause a noise problem during the night, an external contact
input (low-noise input) can be used to operate the outdoor fan and compressor at low speed. This reduces
the operating noise by approximately 2 to 3 dB.
Action During Low
Noise Operation
(Except Oil Return,
Defrost)
1 Discharge pressure
≤
24k
2 Discharge pressure > 24k
External control adaptor for outdoor unit is required to the low noise control (OPTION)
4.15.2 Demand Control
By connecting the external contact input to the Demand control input of the outdoor unit external control
adaptor(option), you can save power with limit of compressor frequency.
Upper Limit of
Compressor
Frequency in
Demand Control
(k:kg/cm
²
)
Conditions
Outdoor Fan
Limit of compressor freguency
INV outdoor unit
STD outdoor unit
1
H + OFF
96Hz + OFF
ON + OFF
2
L + ON
(k:kg/cm
²
)
3 outdoor units
2 outdoor units
Capacity saving
RX(Y) 24 ~ 30K
REY 24 ~ 30K
(24 ~ 30Hp)
RX(Y) 16 ~ 20K
REY 16 ~ 20K
(16 ~ 20Hp)
Demand input 1
INV (106 + ON)
STD1 (ON + OFF)
STD2 (ON + OFF)
INV (106 + ON)
STD (ON + OFF)
Power comsumption will be
reduced to around 70% of
normal usage.
Demand input 2
INV (60 + ON)
STD1 (ON + OFF)
STD2 (OFF + OFF)
INV (106 + OFF)
STD (OFF + OFF)
Power comsumption will be
reduced to around 40% of
normal usage.
Demand input 3
Forced thermostat OFF
Not run
SI-05C.BOOK Page 240 Monday, November 6, 2000 4:13 PM