Outline of Control
SiE-05C
244
Functions PLUS Series
4.18
Emergency Operation
4.18.1 Emergency Operation 1
If INV outdoor unit cannot operate, you can operate with STD outdoor units only if the outdoor temperature
doesn’t exceed the reference temperature. Emergency operation is executed by setting mode 2 to EMG
(emergency operation).
When Cooling (For Heat Pump System)
Indoor Unit Fan Control
HPS operation for either STD outdoor unit 1 or 2
→
Fixed to L tap ON by thermostat unit only.
When Cooling
Control IN conditions &
Emergency operation setting
Outdoor temperature detected to be above 20˚C
for STD outdoor unit 1
: Operates No. 1 compressors only of STD outdoor unit 1 and 2.
: Operates all compressors of STD outdoor unit 1 and 2.
Step 1
Step 2
Oil return
Comp-
ressor
Outdoor
unit fan
Outdoor
unit EEV
Hot gas bypass
INV outdoor
unit
STD outdoor
unit 1
STD outdoor
unit 2
5 minutes elapse
Liquid pipe temp.
of STD outdoor unit 2 < 58˚C
Liquid pipe temp. STD outdoor unit 1 > 60˚C
Indoor units execute superheating
control in this mode.
0 Hz + OFF
H + ON
0 PLS
ON
ON + OFF
H + ON
2000 PLS
OFF
ON + OFF
H + ON
2000 PLS
OFF
Comp-
ressor
Outdoor
unit fan
Outdoor
unit EEV
Hot gas bypass
INV outdoor
unit
STD outdoor
unit 1
STD outdoor
unit 2
0 Hz + OFF
H + ON
0 PLS
ON
ON + ON
H + ON
2000 PLS
OFF
ON + ON
H + ON
2000 PLS
OFF
Comp-
ressor
Outdoor
unit fan
Outdoor
unit EEV
Hot gas bypass
INV outdoor
unit
STD outdoor
unit 1
STD outdoor
unit 2
0 Hz + OFF
H + ON
0 PLS
ON
ON + OFF
H + ON
2000 PLS
OFF
ON + OFF
H + ON
2000 PLS
OFF
Compressors operate total of 70 min.
following previous oil return.
: Operates by executing oil return for standard types 1 and 2.
Either malfunction, retry or outdoor temp. < 15˚C
Quit
3 minutes elapse
(VF123)
SI-05C.BOOK Page 244 Monday, November 6, 2000 4:13 PM