SiE-05C
Outline of Control
Functions PLUS Series
249
4.19.2 In Case of Cooling Only System
Pump Down
Operation of INV
Outdoor Unit
First fully close the liquid side and pressure equalizing side stop valves of the INV outdoor unit. The
execute low pressure control by setting indoor unit fan to L or off in accordance with the outdoor
temperature and No. 2 system outdoor unit suction pipe temperature.
Pump Down
Operation of STD
Outdoor Unit
First fully close the liquid side and pressure equalizing side stop valves of the STD outdoor unit to be
pumped down. The indoor unit fan is fixed at L tap.
To pump down refrigerant of STD outdoor unit 1
Normal cooling operation is executed by INV outdoor unit and STD outdoor unit 2 only.
To pump down refrigerant of STD outdoor unit 2:
Normal cooling operation is executed by INV outdoor unit and STD outdoor unit 1 only.
Outdoor unit operation is same as STD outdoor unit 1.
: Operates No. 1 compressors only of STD outdoor unit 1 and 2.
Step 1
Comp-
ressor
Outdoor
unit fan
Function unit's solenoid
INV outdoor
unit
STD outdoor
unit 1
STD outdoor
unit 2
0 Hz + OFF
H + ON
Y5-ON
ON + OFF
H + ON
Y6-OFF
ON + OFF
H + ON
Y7-OFF
Step 2
Comp-
ressor
Outdoor
unit fan
Function unit's solenoid
INV outdoor
unit
STD outdoor
unit 1
STD outdoor
unit 2
0 Hz + OFF
H + ON
Y5-ON
ON + ON
H + ON
Y6-OFF
ON + ON
H + ON
Y7-OFF
Indoor units execute
superheating control in this
mode.
l
No. 2 outdoor unit liquid pipe temp.
below 58˚C
&
l
5 minutes elapse
STD outdoor unit 2 liquid
pipe temp. above 60˚C
: Operates all compressors of STD outdoor unit 1 and 2.
(VF127)
Comp-
ressor
Outdoor
unit fan
Function unit's solenoid
INV outdoor
unit
STD outdoor
unit 1
STD outdoor
unit 2
P I control
H + ON
OFF
H + ON
Y6-ON
P I control
H + ON
Low pressure
protection control
Low pressure
protection control
Indoor units execute
superheating control in this
mode.
(VF171)
SI-05C.BOOK Page 249 Monday, November 6, 2000 4:13 PM