SiE-05C
Test Operation
Test Operation PLUS Series
281
1.5.2
Setting Mode 2
To switch from setting mode 1 (normal) to setting mode 2, you must push and hold the next page button
(BS1) for 5 seconds. (You cannot enter setting mode 2 while setting mode 1 is set.)
Setting Procedure
1. Push the SET button and match with the setting item (LED display). (All 10 settings)
2. Push the RETURN button (BS3) and the present settings flicker (LED display).
3. Push the SET button (BS2) and match with each setting (LED flicker display).
4. Push the RETURN button (BS3) and enter the settings.
5. Push the RETURN button (BS3) and return to the initial status.
Note:
1. If you become unsure of how to proceed, push the MODE button (BS1) and return to setting mode 1.
2. The initial status of setting mode 2 is the status of setting item No. 1 in mode 2.
SI-05C.BOOK Page 281 Monday, November 6, 2000 4:13 PM
Все каталоги и инструкции здесь:
http
:
//splitoff.ru/tehn-doc.html