Test Operation
SiE-05C
282
Test Operation PLUS Series
Setting Items
Note:
TC setting and Defrost setting are not applicable to cooling only system.
Setting item
EMG
(Emergency
operation 1)
Cool/heat
unified address
Low noise /
demand
address
Forced fan
switch
Indoor unit
forced
operation
Frequency fix
TE setting
TC setting
Note 1
Defrost setting
Note 1
Air NET
address
Pump down
operation 1
Pump down
operation 2
Pump down
operation 3
Forced backup
operation
(Emergency
operation 2)
~
~
~
Description
Emergency
operation when
inverter type
outdoor unit
malfunctions.
Address for
cool/heat
unified
operation
Address for
low noise /
demand
operation.
Indoor unit fan
turns while unit
is stopped.
Allows operation of
indoor unit from
outdoor unit.
Fixes compressor
frequency.
INV : (60Hz+OFF)
STD1: (ON+OFF)
STD2: (ON+OFF)
Low pressure
setting for
cooling.
High pressure
setting for
heating
Temperature
setting for
defrost.
Address for
Air NET
Pump down
operation of
INV outdoor
unit.
Pump down
operation of STD
1 outdoor unit.
Pump down
operation of STD
2 outdoor unit.
Executes
emergency
operation when
constant speed
outdoor unit is
faulty.
LED display
H1P H2P H3P H4P H5P H6P H7P
Emergency operation
(Operates by constant speed outdoor unit
only.)
Normal operation
Address
Binary number
(5 digits)
Address
Binary number
(5 digits)
Forced fan operation
(H tap)
Normal operation
Indoor unit forced
operation
Normal operation
Frequency fix
Normal operation
High
Normal (factory set)
Low
Quick defrost
Normal (factory set)
Slow defrost
Address
Binary number
(6 digits)
Pump down operation
Normal operation
When constant speed
outdoor unit 2 is faulty:
When constant speed
outdoor unit 1 is faulty:
Normal operation
(VF169)
LED display
H1P H2P H3P H4P H5P H6P H7P
0
1
2
31
0
1
2
31
0
1
2
63
1
2
3
4
5
6
7
8
9
10
11
12
13
14