Test Operation
SiE-05C
290
Test Operation PLUS Series
1.8
Cool/Heat Mode Switching (
∗
Except for Cooling Only System)
The VRV PLUS Series cool/heat switching system offers the following 4 cool/heat modes.
1. Set cool/heat separately for each outdoor system by indoor unit remote controller.
2. Set cool/heat separately for each outdoor system by cool/heat selector.
3. Set cool/heat for more than one outdoor unit system simultaneously in accordance with unified master
outdoor unit by indoor unit remote controller.
4. Set cool/heat for more than one outdoor unit system simultaneously in accordance with unified master
outdoor unit by cool/heat selector.
Details of each setting mode are explained below.
(For modes 3 and 4, perform power supply reset of the outdoor unit external control adaptor after changing
the setting.
1.8.1
Set Cool/Heat Separately for Each Outdoor System by Indoor Unit Remote Controller.
It doesn’t matter whether or not there is outdoor - outdoor unit wiring.
Set function unit PC board SS1 to “indoor” (factory set).
Set cool/heat switching to “individual” for setting mode 1 (factory set).