Troubleshooting
SiE-05C
306
Troubleshooting PLUS Series
3.7
Outdoor Unit: Abnormal Discharge Pipe Temperture
Remote Controller
Display
FFFF3333
Supposed Causes
Abnormal discharge pipe temperature
Defect of discharge pipe thermistor (5K: R3T 8K, 10K: R3-1T, R3-2T)
Defect of outdoor unit PC board
Discharge pipe thermistor wrong connection
Liquid injection solenoid valve wrong connection
Trobleshooting
Troubleshooting the outdoor unit for which HWL is lit in accordance with the following flow chart.
Discharge
pipe temperature is 135˚C
or higher.
NO
8, 10K:
Is there a wrong
connection of the injection
solenoid valves Y2S
and Y3S?
8, 10K:
Is there a wrong connection of the
discharge pipe thermistor?
•
INV outdoor unit
R3-1T (inverter side) X17A
R3-2T (standard side) X18A
•
Constant speed outdoor unit
R3-1T (standard 1 side) X17A
R3-2T (standard 2 side) X18A
Are the
characteristics of the
discharge pipe thermistor
normal? (3.5k
Ω
~
400k
Ω
)
YES
NO
NO
NO
YES
YES
YES
Connect correctly and turn on again.
Out of gas, compression defect, etc.
Defect of the refrigerant system
Replace the discharge pipe
thermistor.
Replace outdoor unit PC board.
INV outdoor unit : A1P
Constant speed outdoor unit : A1P
(VF141)
SI-05C.BOOK Page 306 Monday, November 6, 2000 4:13 PM