Troubleshooting
SiE-05C
314
Troubleshooting PLUS Series
3.18
Low Pressure Drop Due to Refrigerant Shortage or Electronic Expansion
Valve Failure
Remote Controller
Display
UUU
U000
0
Supposed Causes
Out of gas or refrigerant system clogging (incorrect piping)
Defect of thermistor (R2T, R4T) of INV outdoor unit
Defect of low pressure sensor of INV outdoor unit
Defect of outdoor unit PC board of INV outdoor unit
Troubleshooting
Troubleshoot the outdoor unit for which the HWL is lit in accordance with the following flow chart.
Cooling
The suction
pipe temperature minus
coil temperature is 20˚C
or higher.
NO
Resistance
is normal when
measured with the suction
pipe thermistor (R4T) and coil
thermistor (R2T) disconnected
from the outdoor unit
PC board.
YES
YES
NO
The
voltage of
X21A pins (2) and
(3) on both sides of outdoor
unit PC board (A1P)
is 0.8 VDC
or less.
Low pressure is
1.0 kg/cm² (0.098 MPa)
or less.
NO
YES
YES
NO
NO
YES
Out of gas or refrigerant system is
clogged. Requires check of
refrigerant system.
Replace outdoor unit PC board.
Replace low pressure sensor.
Out of gas or refrigerant system is
clogged. Requires check of
refrigerant system.
Replace the thermistor.
Replace the outdoor unit PC board :
A1P
(VF152)
SI-05C.BOOK Page 314 Monday, November 6, 2000 4:13 PM